Each boiler feed pump on a deaerator is sized based on the total load of boilers fed by the specific pump.
For boiler feed pumps running ON/OFF, the pumps are controlled by a boiler level controller.
Each transfer pump on surge chamber is sized based on total load of deaerator plus additional water to feed vent condensor that is included on atmospheric design.
If boiler and deaerator are on the same floor, enter a value of "0" for feet of head. If boiler is located on a floor above the deaerator, enter vertical height (in feet) from the pump discharge on the deaerator up to the inlet piping on the boiler.
Assumes pressure drop through modulating valve of 10 psig or less.
Assumes pressure drop through stack economizer of 20 psig or less.
Assumes proper discharge pipe size of a velocity of 10 ft/sec or less.
Pump discharge pressure must be able to overcome the relief valve setting of the boiler. Relief valve setting on the boiler should be adjusted or replaced so the setting of the relief valve is close to the actual operating pressure of the boiler.
The receiver size on 2-chamber deaerators is typically based on the total system load (i.e. sum of all boilers fed by deaerator) with 20 minutes NET storage—10 minutes for deaerator chamber and 10 minutes for surge chamber.
Pump discharge pressure MUST BE ABLE to overcome the boiler safety relief valve setting plus three percent of valve setting AND meet all state and local codes.
If the pressure differential between the boiler operating pressure and the setting of the safety relief valve on the boiler is greater than 20 psig, consider replacing the safety valve with one rated closer to the boiler operating pressure. Otherwise the motor horsepower of the boiler feed pumps will need to be oversized to provide a discharge pressure sufficient to overcome the rating of the safety relief valve on the boiler. The higher motor HP typically would require a more expensive pump and increases ongoing operating costs.